Enter a reading
1
Choose how to get it in
Type it, paste the ATG report text, upload the report file, or use
Scan ATG inventory report to read a printout.
2
Enter the closing figures
Opening and closing gross and net gallons, sales gallons, deliveries,
closing temperature and water level.
3
Submit
The reconciliation is calculated immediately.
How the variance is read
The arithmetic is: opening + deliveries − sales = expected, compared against what the tank actually holds. The difference is then broken into causes:
Unexplained variance is the number to watch. It is the theft or leak
indicator, and it is the reason the other causes are separated out at all — a
raw variance figure hides a real problem inside normal thermal movement.
You record the suspected cause on each reconciliation, including
THEFT_UNAUTHORIZED_DISPENSE and UNDERGROUND_TANK_LEAK.
The EPA log
Fuel Operations → EPA Log shows each day’s Date, Tank, Book Inventory, ATG Physical, Total Variance, Thermal, Unexplained, Cause and EPA status. The monthly compliance test is applied for you: the variance must be within 1% of throughput plus 130 gallons. Each period is flagged compliant or not.A persistent unexplained variance in one direction is worth acting on quickly.
Repeated water readings, or a steady loss that survives the thermal
correction, are exactly what this page exists to surface.